SQ系列供水系統是由B/P型控制(zhi)柜(ju)控制(zhi)和(he)管(guan)理的供水(shui)設備。該控制(zhi)柜(ju)與各種不同類型的傳感器連接,在設定供水(shui)壓力(li)范圍內,根據(ju)客戶(hu)壓力(li)的要求(qiu),水(shui)泵逐個自動投入運(yun)行或關閉(bi)。

設備通電(dian)后5s后(hou)變頻(pin)器開始工(gong)作(zuo),由壓(ya)力傳感器給定的反饋(kui)值與設定的目標值作(zuo)PID運算(suan)后,產生運行頻(pin)率,對(dui)壓力(li)進行動態監(jian)控保證壓力(li)穩(wen)定。當用水量持續增(zeng)加,超過單臺的供(gong)水能力(li)時,變頻(pin)器處于48Hz以上持續(xu)20s未能達(da)到設(she)定(ding)壓(ya)力,并有壓(ya)力下降的趨勢,設(she)備(bei)將自動增加一(yi)臺(tai)水(shui)泵投(tou)入(ru)運行,以(yi)保證壓(ya)力達(da)到設(she)定(ding)值。當用水(shui)量減少(shao)時,變頻(pin)器處于35Hz以下低頻運行持續15s,頻(pin)率未能升高,設備(bei)通過計算(suan)比較(jiao)后,將自動減少一臺水泵投(tou)入運行,當單臺泵低(di)頻(pin)小于30Hz持(chi)續60s時,控(kong)制系統將進入休眠模式,壓力降低后(hou)系統會自動被喚醒重新工作。
可以(yi)說變(bian)頻(pin)(pin)供(gong)(gong)水(shui)(shui)(shui)(shui)是根據用(yong)戶(hu)用(yong)水(shui)(shui)(shui)(shui)量(liang)變(bian)化自(zi)動調節運(yun)行(xing)(xing)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)一臺(tai)和(he)數臺(tai)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)轉速(su),使(shi)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)出(chu)(chu)(chu)口壓(ya)力在一定范圍內(nei)保(bao)(bao)持恒定。當(dang)用(yong)戶(hu)用(yong)水(shui)(shui)(shui)(shui)量(liang)小于(yu)一臺(tai)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)出(chu)(chu)(chu)水(shui)(shui)(shui)(shui)量(liang)時(shi)(shi),系(xi)(xi)統根據用(yong)水(shui)(shui)(shui)(shui)量(liang)變(bian)化有一臺(tai)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)變(bian)頻(pin)(pin)調速(su)運(yun)行(xing)(xing),當(dang)用(yong)水(shui)(shui)(shui)(shui)量(liang)增加時(shi)(shi)管道(dao)系(xi)(xi)統內(nei)壓(ya)力下降,這時(shi)(shi)壓(ya)力傳感器(qi)把檢測(ce)到的(de)信號(hao)傳送給微機控制單元,通過微機運(yun)行(xing)(xing)判斷,發(fa)出(chu)(chu)(chu)指令到變(bian)頻(pin)(pin)器(qi),控制水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)電(dian)機,使(shi)轉速(su)加快(kuai)以保(bao)(bao)證(zheng)系(xi)(xi)統壓(ya)力恒定,反之當(dang)用(yong)水(shui)(shui)(shui)(shui)量(liang)減少時(shi)(shi),使(shi)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)轉速(su)減慢,以保(bao)(bao)持恒壓(ya)。當(dang)用(yong)水(shui)(shui)(shui)(shui)量(liang)大于(yu)一臺(tai)泵(beng)(beng)(beng)出(chu)(chu)(chu)水(shui)(shui)(shui)(shui)量(liang)時(shi)(shi),第(di)一臺(tai)泵(beng)(beng)(beng)切換到工(gong)頻(pin)(pin)運(yun)行(xing)(xing),第(di)二臺(tai)泵(beng)(beng)(beng)開始變(bian)頻(pin)(pin)調速(su)運(yun)行(xing)(xing),當(dang)用(yong)水(shui)(shui)(shui)(shui)量(liang)小于(yu)兩臺(tai)泵(beng)(beng)(beng)出(chu)(chu)(chu)水(shui)(shui)(shui)(shui)量(liang)時(shi)(shi),能自(zi)動停止一臺(tai)或二臺(tai)泵(beng)(beng)(beng)運(yun)行(xing)(xing)。在整個運(yun)行(xing)(xing)過程中(zhong),始終保(bao)(bao)持系(xi)(xi)統恒壓(ya)不變(bian),使(shi)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)始終工(gong)作(zuo)(zuo)在高效區,既保(bao)(bao)證(zheng)用(yong)戶(hu)恒壓(ya)供(gong)(gong)水(shui)(shui)(shui)(shui),又節省電(dian)能。設備不需配(pei)備專職(zhi)操作(zuo)(zuo)人員。
如(ru)果您(nin)要采購變頻供水設備,以下是喜之(zhi)泉總結的選(xuan)型(xing)須知(zhi):
- 自來水(shui)進水(shui)量應(ying)大于或等于供水(shui)量
2、當自來水壓(ya)力小于0.05MPa時,進水(shui)流(liu)量無法滿足(zu)水(shui)泵吸水(shui)流(liu)量,同時又需(xu)啟動水(shui)泵增(zeng)加(jia)壓力,就需(xu)要(yao)設計流(liu)調節(jie)水(shui)箱(即箱式無負壓)
3、選型參數按(an)每戶3.5人(ren),每人(ren)每天用水165L,高(gao)峰供水(shui)水(shui)量乘以4倍計算(suan)
4、賓館用水量(liang)按房間數量(liang)的80%計算,房間用水量為120L,一般中小(xiao)規模的經(jing)營性餐廳廚房日(ri)用水量3000L
5、為了更加節能減排(pai)的需要,小(xiao)(xiao)區流量(liang)變化大的使用(yong)場(chang)合,在夜間或小(xiao)(xiao)流量(liang)時供水時間長的場(chang)合,建議增加一臺小(xiao)(xiao)流量(liang)泵(beng)。小(xiao)(xiao)泵(beng)的揚程高于大泵(beng)10%~20%,流(liu)量是大泵的10%-15%