日韩精品无码一区二区三区av,中文字幕亚洲乱码熟女一区二区,精品无人码麻豆乱码1区2区,在线观看成人网站,XXX波多野结衣XXXM

 您的當前位置: 首頁 > 新聞資訊 > 技術文章

消防泵故障消除措施以及消防泵控制怎么設置

2021/12/20

通常在(zai)檢修過程(cheng)中,消(xiao)(xiao)防泵故(gu)障(zhang)的(de)(de)診斷(duan)是(shi)一個關鍵的(de)(de)環節(jie),以下給出幾種常見故(gu)障(zhang)及(ji)消(xiao)(xiao)除(chu)措(cuo)施,供大家有的(de)(de)放矢地(di)進行(xing)消(xiao)(xiao)防泵故(gu)障(zhang)的(de)(de)診斷(duan)。

  1、無液體提供,供給液體不足或壓力不足

  1)泵(beng)沒有注水或沒有適當排氣 消除措(cuo)施:檢(jian)查泵(beng)殼和入口管線(xian)是(shi)否全部注滿(man)了(le)液體。

  2)速度太低 消除(chu)措(cuo)施(shi):檢查電機的接(jie)線是(shi)否(fou)正確,電壓(ya)是(shi)否(fou)正常或者透平的蒸(zheng)汽(qi)壓(ya)力是(shi)否(fou)正常。

  3)系(xi)統水頭(tou)太高 消除措施:檢查系(xi)統的水頭(tou)(特別是磨擦損失)。

  4)吸程太高 消除措施(shi):檢查現(xian)有(you)的凈壓頭(入口管線太小或太長會(hui)造成很(hen)大的磨擦損失)。

  5)葉輪或管線受堵 消除措(cuo)施:檢查有(you)無障礙(ai)物。

  6)轉(zhuan)動(dong)方(fang)向不對 消除(chu)措施:檢查轉(zhuan)動(dong)方(fang)向。

  7)產生空氣或(huo)入口管線(xian)有泄漏 消除措施:檢查入口管線(xian)有無氣穴和/或(huo)空氣泄漏。

  8)填(tian)(tian)料(liao)函(han)中(zhong)(zhong)的(de)填(tian)(tian)料(liao)或密封磨損,使空氣漏入泵殼中(zhong)(zhong) 消除措施:檢(jian)查(cha)填(tian)(tian)料(liao)或密封并按需要更換,檢(jian)查(cha)潤滑是否正常。

  9)抽送熱的(de)或揮發性液體時吸入水頭不足(zu) 消除措施:增大吸入水頭,向(xiang)廠家咨詢(xun)。

  10)底閥太小 消除措施(shi):安裝正(zheng)確尺寸的底閥。

  11)底閥或(huo)入口管(guan)浸沒(mei)深(shen)度不夠 消除(chu)措施(shi):向廠家咨詢正確(que)的浸沒(mei)深(shen)度。用擋板消除(chu)渦(wo)流。

第一種接口控(kong)制(zhi)(zhi)(zhi)方式(shi):消防模塊(kuai)輸出DC24V有源信號控(kong)制(zhi)(zhi)(zhi)(也就是指消防模塊(kuai)邏輯啟(qi)泵,按照廠家(jia)提供的控(kong)制(zhi)(zhi)(zhi)柜原理圖紙(zhi)這種控(kong)制(zhi)(zhi)(zhi)方式(shi)可以實現主備泵故障互投(tou)功能,也就是說(shuo)用一個模塊(kuai)控(kong)制(zhi)(zhi)(zhi)自動啟(qi)泵,這個我們認(ren)為種控(kong)制(zhi)(zhi)(zhi)方式(shi)能夠符合(he)消防有關規范,是合(he)理的)。

  第二(er)種接(jie)口控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)方(fang)(fang)式:應急控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)(從消(xiao)(xiao)防(fang)(fang)控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)中(zhong)心硬拉(la)線(xian)(xian)(xian)到水(shui)泵(beng)控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)柜):請問這種應急控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)方(fang)(fang)法是按(an)照水(shui)泵(beng)控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)柜控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)(每個(ge)泵(beng)控(kong)(kong)(kong)(kong)(kong)柜只(zhi)做一組硬拉(la)線(xian)(xian)(xian)控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)),還是按(an)照水(shui)泵(beng)控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)(每臺泵(beng)留一個(ge)接(jie)口用(yong)三(san)組硬拉(la)線(xian)(xian)(xian)分別控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)三(san)臺泵(beng)的(de)啟(qi)停)? 這種控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)方(fang)(fang)式說(shuo)的(de)更明(ming)白一點(dian)就是請問:“消(xiao)(xiao)防(fang)(fang)應急控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)(硬拉(la)線(xian)(xian)(xian)控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi))”是否(fou)需(xu)要經(jing)過(guo)泵(beng)控(kong)(kong)(kong)(kong)(kong)柜內(nei)互投切(qie)換電路控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)還是直接(jie)通(tong)過(guo)消(xiao)(xiao)防(fang)(fang)控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)中(zhong)心的(de)各自齊泵(beng)按(an)鈕強(qiang)行(xing)啟(qi)泵(beng)?若采用(yong)消(xiao)(xiao)防(fang)(fang)控(kong)(kong)(kong)(kong)(kong)制(zhi)(zhi)中(zhong)心按(an)鈕強(qiang)行(xing)啟(qi)泵(beng)的(de)方(fang)(fang)式能通(tong)過(guo)消(xiao)(xiao)防(fang)(fang)局(ju)驗收嗎?如不能通(tong)過(guo),哪(na)里有(you)相關(guan)的(de)規范來證(zheng)明(ming)這個(ge)問題?

  第(di)三種接(jie)口(kou)控(kong)制(zhi)方(fang)式:通過報警閥(fa)上(shang)的壓(ya)力開關動作后聯動啟泵,這種控(kong)制(zhi)方(fang)式暫時不考慮,在此只是做(zuo)控(kong)制(zhi)說(shuo)明。

  二、消防泵(beng)的(de)啟動通常有以下幾種:

  一、水泵(beng)房消防泵(beng)控制柜(ju)直(zhi)接啟泵(beng)。

  二(er)、消防報警主(zhu)機多線(xian)(xian)模(mo)塊(kuai)啟動,報警主(zhu)機的面(mian)板上(shang)有一個多線(xian)(xian)控制盤,上(shang)面(mian)相應的啟停按鈕,也就是您說的第一種情(qing)況。

  三、依靠(kao)管網壓力(li)的(de)(de)變化(hua)來控制啟停泵,包括:電接點壓力(li)表,壓力(li)開(kai)關等(deng)就是這種(zhong)情況。這也就是您所(suo)說(shuo)的(de)(de)第(di)三種(zhong)情況。